Jack’s Code Corner: NFPA 25 – 2017 Change in Evaluation of Fire Pump Test Results
In the 2017 edition of NFPA 25, Chapter 8 (Fire Pumps), there was a significant change from the previous editions of the evaluation of Fire Pump Test Results.
In the 2014 and previous editions, the Pump Evaluation (pass/fail) was determined at the 100% flow rate with a degradation of no more than 95 percent. In the 2017 through current editions, the Evaluation criteria (pass/fail) now require review at EACH required flow point.
Evaluations of: Churn, Rated and Overload, shall be evaluated for no less than 95 percent of flow rates and pressure at each point for either Original unadjusted field test curve, or the Fire pump nameplate. See section 8.3.7.2 of the 2017 NFPA 25, with more explanatory material in the 2017 NFPA 25 Handbook.

In the fire protection industry, inspections are more than a compliance checkbox—they’re the gateway to stronger customer relationships, more predictable revenue, and a more efficient service operation. But for too long, inspections have been riddled with delays and disruptions, fragmented systems, and manual processes that limit your team’s productivity and profitability. That’s why we built […]
In a competitive commercial service market, landing maintenance agreements is your most valuable strategy for strengthening customer relationships and building future revenue streams. Sales reps and account managers are the face of your business to the customer, and they need easier ways to propose equipment maintenance agreements and provide accurate quotes for required repairs or […]