Jack’s Code Corner: NFPA 25 – 2017 Change in Evaluation of Fire Pump Test Results
In the 2017 edition of NFPA 25, Chapter 8 (Fire Pumps), there was a significant change from the previous editions of the evaluation of Fire Pump Test Results.
In the 2014 and previous editions, the Pump Evaluation (pass/fail) was determined at the 100% flow rate with a degradation of no more than 95 percent. In the 2017 through current editions, the Evaluation criteria (pass/fail) now require review at EACH required flow point.
Evaluations of: Churn, Rated and Overload, shall be evaluated for no less than 95 percent of flow rates and pressure at each point for either Original unadjusted field test curve, or the Fire pump nameplate. See section 8.3.7.2 of the 2017 NFPA 25, with more explanatory material in the 2017 NFPA 25 Handbook.

What does the future look like for fire and life safety contractors? At the 2025 NAFED Conference, the message was clear: the future belongs to smart, scalable, technician-first businesses. From cutting-edge tech to old-school fundamentals that still matter, this year’s sessions offered practical insights for contractors ready to grow. Here are five key takeaways that […]
If you’ve ever watched a Roomba spend 20 minutes trying to escape from under a chair and thought, “This is the tech that’s supposed to be smarter than humans?”—you’re not alone. Or maybe you saw the viral story where AI suggested using glue to keep cheese on pizza (yes, really), and figured the whole thing […]