Jack’s Code Corner: NFPA 25 – 2017 Change in Evaluation of Fire Pump Test Results
In the 2017 edition of NFPA 25, Chapter 8 (Fire Pumps), there was a significant change from the previous editions of the evaluation of Fire Pump Test Results.
In the 2014 and previous editions, the Pump Evaluation (pass/fail) was determined at the 100% flow rate with a degradation of no more than 95 percent. In the 2017 through current editions, the Evaluation criteria (pass/fail) now require review at EACH required flow point.
Evaluations of: Churn, Rated and Overload, shall be evaluated for no less than 95 percent of flow rates and pressure at each point for either Original unadjusted field test curve, or the Fire pump nameplate. See section 8.3.7.2 of the 2017 NFPA 25, with more explanatory material in the 2017 NFPA 25 Handbook.

Choosing software for your fire protection business is one of the most important decisions you’ll make. The right platform should simplify daily operations, ensure compliance, and scale with your growth—not slow your team down with wasted effort, risky gaps, or endless configuration. Unfortunately, not every solution on the market delivers on those promises. For more […]
After years of building a successful commercial mechanical service business, many owners eventually face the question: “What’s next?” Whether you’re looking to retire, pursue new ventures, or simply cash in on your hard work, if selling your business is the right choice for you, having a clear exit strategy is crucial for maximizing your business […]